How often does fire safety equipment need testing?

Every routine check for a typical non-domestic building, how often it is due and who should do it.

Fire safety equipment only protects people if it is tested and maintained. British Standards set out how often each system should be checked, and the Fire Safety Order makes the responsible person accountable for getting it done and keeping records.

How oftenWhatWho does itStandardOur service
Every weekFire alarm test, using a different call point each timeTrained staff, or usBS 5839-1Weekly & Monthly Testing
Every weekSprinkler system checks (commercial systems)Trained staffBS EN 12845Sprinkler Servicing
Every monthEmergency lighting short function testTrained staff, or usBS 5266-1Weekly & Monthly Testing
Every monthVisual check of fire extinguishersTrained staffBS 5306-3Fire Extinguishers
Every 3 monthsCommunal fire door checks (residential buildings in England with a storey above 11 m)Responsible person, or usFire Safety (England) Regulations 2022Fire Door Inspections
Every 3 monthsSprinkler inspection (commercial systems)Competent engineerBS EN 12845Sprinkler Servicing
Every 6 monthsFire alarm serviceCompetent engineerBS 5839-1Fire Alarms
Every 6 monthsDry riser visual inspectionCompetent engineerBS 9990Dry Riser Servicing
Every 6 to 12 monthsKitchen fire suppression service, at the interval the manufacturer setsCompetent engineerBS EN 17446Kitchen Fire Suppression
Every yearFire extinguisher serviceCompetent engineerBS 5306-3Fire Extinguishers
Every yearEmergency lighting full-duration testCompetent engineerBS 5266-1Emergency Lighting
Every yearDry riser wet pressure testCompetent engineerBS 9990Dry Riser Servicing
Every yearSprinkler system annual inspectionCompetent engineerBS EN 12845 / BS 9251Sprinkler Servicing
Every yearSmoke vent (AOV) serviceCompetent engineerBS 9999 / BS 7346-8Smoke Vent Servicing
Every yearFire damper drop test (spring-operated dampers; more often in dusty areas)Competent engineerBS 9999Fire Damper Servicing
Every yearFlat entrance fire door checks (residential buildings in England with a storey above 11 m)Responsible person, or usFire Safety (England) Regulations 2022Fire Door Inspections
Every year (recommended)Fire risk assessment reviewCompetent assessorFire Safety OrderFire Risk Assessments
Every year (recommended)Staff fire safety training refresherCompetent trainerFire Safety OrderFire Training
When things changeReview the risk assessment, signage and extinguisher coverCompetent assessorFire Safety OrderFire Risk Assessments

A guide, not a substitute for your risk assessment

This table covers the usual checks for a typical building in England. Your fire risk assessment may call for more, and some equipment has extra tests at five or ten years.

If you are not sure what applies to you, call 0161 620 7346 and we will tell you.

Write everything down

Every test, fault and repair goes in the fire log book. It is the first thing a fire officer or insurer asks to see.

Know who does what

Weekly and monthly checks can be done by trained staff. Servicing and annual tests need a competent engineer.

Let us run the calendar

We can take on the whole schedule, carry out each visit and remind you before anything is due.

Want us to manage your testing schedule?

Call 0161 620 7346 or send us a message.