How often does fire safety equipment need testing?
Every routine check for a typical non-domestic building, how often it is due and who should do it.
Fire safety equipment only protects people if it is tested and maintained. British Standards set out how often each system should be checked, and the Fire Safety Order makes the responsible person accountable for getting it done and keeping records.
| How often | What | Who does it | Standard | Our service |
|---|---|---|---|---|
| Every week | Fire alarm test, using a different call point each time | Trained staff, or us | BS 5839-1 | Weekly & Monthly Testing |
| Every week | Sprinkler system checks (commercial systems) | Trained staff | BS EN 12845 | Sprinkler Servicing |
| Every month | Emergency lighting short function test | Trained staff, or us | BS 5266-1 | Weekly & Monthly Testing |
| Every month | Visual check of fire extinguishers | Trained staff | BS 5306-3 | Fire Extinguishers |
| Every 3 months | Communal fire door checks (residential buildings in England with a storey above 11 m) | Responsible person, or us | Fire Safety (England) Regulations 2022 | Fire Door Inspections |
| Every 3 months | Sprinkler inspection (commercial systems) | Competent engineer | BS EN 12845 | Sprinkler Servicing |
| Every 6 months | Fire alarm service | Competent engineer | BS 5839-1 | Fire Alarms |
| Every 6 months | Dry riser visual inspection | Competent engineer | BS 9990 | Dry Riser Servicing |
| Every 6 to 12 months | Kitchen fire suppression service, at the interval the manufacturer sets | Competent engineer | BS EN 17446 | Kitchen Fire Suppression |
| Every year | Fire extinguisher service | Competent engineer | BS 5306-3 | Fire Extinguishers |
| Every year | Emergency lighting full-duration test | Competent engineer | BS 5266-1 | Emergency Lighting |
| Every year | Dry riser wet pressure test | Competent engineer | BS 9990 | Dry Riser Servicing |
| Every year | Sprinkler system annual inspection | Competent engineer | BS EN 12845 / BS 9251 | Sprinkler Servicing |
| Every year | Smoke vent (AOV) service | Competent engineer | BS 9999 / BS 7346-8 | Smoke Vent Servicing |
| Every year | Fire damper drop test (spring-operated dampers; more often in dusty areas) | Competent engineer | BS 9999 | Fire Damper Servicing |
| Every year | Flat entrance fire door checks (residential buildings in England with a storey above 11 m) | Responsible person, or us | Fire Safety (England) Regulations 2022 | Fire Door Inspections |
| Every year (recommended) | Fire risk assessment review | Competent assessor | Fire Safety Order | Fire Risk Assessments |
| Every year (recommended) | Staff fire safety training refresher | Competent trainer | Fire Safety Order | Fire Training |
| When things change | Review the risk assessment, signage and extinguisher cover | Competent assessor | Fire Safety Order | Fire Risk Assessments |
A guide, not a substitute for your risk assessment
This table covers the usual checks for a typical building in England. Your fire risk assessment may call for more, and some equipment has extra tests at five or ten years.
If you are not sure what applies to you, call 0161 620 7346 and we will tell you.Write everything down
Every test, fault and repair goes in the fire log book. It is the first thing a fire officer or insurer asks to see.
Know who does what
Weekly and monthly checks can be done by trained staff. Servicing and annual tests need a competent engineer.
Let us run the calendar
We can take on the whole schedule, carry out each visit and remind you before anything is due.